Under the Water Industry Act 1991, compressed air condensate discharged to foul sewer must not exceed 20 mg/L total hydrocarbons via approved oil-water separator systems, enforced by Environmental Permitting (England and Wales) Regulations 2016 and PSSR 2000 for pressure vessel isolation. This SOP mandates weekly filter inspection, quarterly coalescer replacement, and annual separator servicing to maintain <20 mg/L discharge compliance, prevent trade effluent consent breaches (fines up to £250,000), and reduce environmental contamination risk from High (5×4=20) to Low (2×2=4) through engineered controls, LOTO isolation, and ISO 14001-aligned monitoring. All maintenance personnel must complete COSHH assessment for hydrocarbon exposure, verify zero-energy state before separator access, and document effluent test results in the site Environmental Management System register to satisfy Water & Sewerage Company (WaSC) audit requirements and UK HSE enforcement expectations.
| Identified Hazard & Harm | Initial Risk (L×S) | Mandatory Engineering, Isolation & Procedural Controls | Residual Risk |
|---|---|---|---|
| 1. Pressurised condensate release during filter housing removal (up to 10 bar residual pressure) Harm: High-velocity oil-water spray causing eye injury, skin injection injury, or inhalation of aerosolised hydrocarbons leading to chemical pneumonitis | 4 × 4 = 16 | Implement PSSR 2000-compliant isolation: close upstream ball valve, open manual drain valve to atmospheric pressure, verify zero pressure via gauge (0 bar) before loosening filter housing. Install bleed valve with clear sight tube. Permit-to-Work required for all separator maintenance. Competent Person (IOSH/NEBOSH qualified) to supervise first-time operatives. | 2 × 2 = 4 |
| 2. Hydrocarbon exposure (dermal/inhalation) during coalescer replacement and sludge disposal Harm: Dermatitis, respiratory irritation, or long-term health effects from repeated mineral oil contact; environmental pollution if spilled to surface water drain | 5 × 3 = 15 | COSHH assessment mandatory (review SDS for mineral oil CAS 8042-47-5). Wear nitrile gloves (BS EN 374) and Type 5/6 coveralls. Work in well-ventilated area (minimum 5 air changes/hour) or use local exhaust ventilation (LEV) if indoors. Dispose of used filters and sludge via licensed waste carrier (EWC 13 05 02*). Provide on-site eyewash station within 10 m. Pre-task toolbox talk on emergency spill procedure. | 3 × 2 = 6 |
| 3. Slips, trips, and falls on oil-contaminated floor around separator (especially during sludge transfer) Harm: Fractures, sprains, or head injury from fall onto concrete floor or adjacent pipework | 4 × 3 = 12 | Place absorbent matting and drip trays under all connection points before opening separator. Clean spills immediately with oil-absorbent granules (minimum 20 L spill kit on-site). Wear S3-rated safety boots with hydrocarbon-resistant, slip-resistant sole (BS EN ISO 20345 SRC). Cordon off work area with barrier tape and warning signs. Ensure adequate lighting (minimum 500 lux at floor level per BS EN 12464-1). | 2 × 3 = 6 |
| 4. Non-compliant effluent discharge (>20 mg/L TPH) leading to trade effluent consent breach and prosecution Harm: Fines up to £250,000 under Environmental Permitting Regulations 2016, WaSC disconnection notice, reputational damage, and environmental harm to watercourses | 3 × 5 = 15 | Test separator effluent monthly using calibrated TPH meter (0–100 mg/L range, annual calibration certificate required). Record results in ISO 14001 Environmental Register. Replace coalescer filter every 3 months or when effluent exceeds 15 mg/L (trigger level). Service separator annually by OEM-approved engineer. Maintain trade effluent consent documentation and submit quarterly monitoring reports to WaSC. Install high-level alarm on separator sump to prevent overflow. | 2 × 3 = 6 |
| 5. Manual handling of heavy filter housings and waste drums (typically 10–25 kg) Harm: Musculoskeletal injury (lower back strain, shoulder injury) from lifting, twisting, or carrying heavy components in confined space | 5 × 2 = 10 | Conduct Manual Handling Operations Regulations 1992 (MHOR) risk assessment. Use two-person lift for filter housings >15 kg. Provide mechanical aids: drum trolley, pallet truck, or hoist for waste drum removal. Position separator at waist height (900–1100 mm) where practicable. Train operatives in safe lifting technique (HSE LITE principles: Load, Individual, Task, Environment). Avoid twisting; pivot feet instead. | 3 × 2 = 6 |
Notify site supervisor and obtain signed Permit-to-Work for oil-water separator maintenance. Isolate compressed air supply by closing upstream ball valve and applying LOTO padlock (BS EN ISO 14118). Open manual drain valve to depressurise separator and filter housing to 0 bar (verify via pressure gauge). Tag valve with 'DO NOT OPERATE' danger tag. Confirm zero-energy state with second competent person (independent verification). Don all mandatory PPE: nitrile gloves (BS EN 374), safety spectacles (BS EN 166), S3 boots (BS EN ISO 20345), and Type 5/6 coveralls.
Collect 100 mL effluent sample from separator outlet (downstream of coalescer) into clean glass bottle. Use calibrated TPH test kit (colorimetric or turbidity method, 0–100 mg/L range) to measure hydrocarbon concentration. Record result in Environmental Management System register with date, time, and operative name. If TPH >20 mg/L, do NOT discharge to sewer—contact WaSC and Environment Agency immediately. If 15–20 mg/L, proceed with coalescer replacement as planned. If <15 mg/L, separator is performing adequately but continue with scheduled maintenance.
Place drip tray and absorbent pads beneath filter housing. Using non-sparking hand tools, loosen filter housing bolts in cross-pattern (torque release sequence) to prevent warping. Carefully remove housing lid and extract coalescer cartridge (typically 5–10 µm micron rating). Allow residual oil-water mixture to drain into drip tray (approximately 1–2 litres). Inspect O-ring seals for damage or compression set; replace if worn. Place used coalescer and contaminated absorbents into UN-approved waste drum labelled 'Hazardous Waste – EWC 13 05 02* – Mineral Oil'. Seal drum and store in bunded area pending collection by licensed waste carrier.
Remove separator sump cover (if applicable) and use hand pump or wet-vac to extract accumulated sludge from bottom of separator chamber. Dispose of sludge as hazardous waste (EWC 13 05 08*). Wipe internal surfaces with lint-free cloth dampened with approved degreaser (check COSHH SDS). Inspect coalescer mounting threads, inlet/outlet ports, and sight glass for cracks, corrosion, or blockages. Check float switch (if fitted) for free movement. Photograph any defects and report to Engineering Manager. If corrosion or structural damage is evident, quarantine separator and arrange replacement.
Fit new OEM-specified coalescer cartridge (verify part number against maintenance schedule). Lubricate new O-ring seals with silicone grease (hydrocarbon-compatible) and seat in housing groove. Refit filter housing lid and torque bolts to manufacturer's specification (typically 25–35 Nm) in cross-pattern sequence using calibrated torque wrench. Close manual drain valve. Remove LOTO padlock and slowly open upstream ball valve to re-pressurise system to operating pressure (typically 7–10 bar). Inspect all joints for leaks using leak detection spray or soapy water. If any leakage observed, re-isolate, depressurise, and re-torque bolts.
Allow separator to run for 15 minutes to stabilise. Collect post-maintenance effluent sample and re-test TPH concentration using calibrated kit. Confirm TPH <15 mg/L (target <10 mg/L for optimal performance). Record result, coalescer part number, and maintenance date in plant logbook and ISO 14001 Environmental Register. Update separator service sticker with next due date (3 months for filter, 12 months for full service). Remove barrier tape and return Permit-to-Work to site supervisor with sign-off. Dispose of all waste via licensed carrier within 72 hours and retain waste transfer note for 3 years (Duty of Care Regulations).
**EMERGENCY CONTACTS:** Site Emergency: [INSERT], Environment Agency Incident Hotline: 0800 807060, Water & Sewerage Company (WaSC): [INSERT LOCAL WASC NUMBER], Poison Centre (NPISonline): 0344 892 0111. **LARGE SPILL (>10 litres):** Evacuate area, activate spill alarm, deploy spill kit and absorbent booms to prevent entry to surface water drains. Notify Environment Agency immediately if risk of watercourse contamination. Contain spill with sand or absorbent granules; do NOT wash down with water. **SKIN CONTACT (mineral oil):** Remove contaminated clothing. Wash affected area with soap and water for at least 15 minutes. Do NOT use solvents or thinners. Seek medical advice if irritation persists. **EYE CONTACT (condensate splash):** Irrigate eyes with eyewash or clean water for at least 15 minutes, holding eyelids open. Remove contact lenses if present. Seek immediate medical attention—risk of chemical conjunctivitis. **INHALATION (hydrocarbon vapour):** Move casualty to fresh air. If breathing is difficult, administer oxygen (if trained). If unconscious, place in recovery position and call 999. Do NOT induce vomiting if oil ingested (aspiration hazard H304). **FIRE:** Separator area may contain flammable oil vapour in ATEX Zone 2. Use CO₂, dry powder, or foam extinguisher—do NOT use water jet. Evacuate and call Fire Service if fire spreads beyond initial stage. **TRADE EFFLUENT BREACH:** If separator fails and non-compliant effluent (>20 mg/L TPH) is discharged, immediately notify WaSC Trade Effluent Officer and Environment Agency. Isolate separator, divert condensate to emergency holding tank (if available), and arrange emergency tankering. Document incident in Environmental Management System and prepare written report within 24 hours. Failure to report is an offence under Environmental Permitting Regulations 2016.
Under the Water Industry Act 1991 and enforced via trade effluent consents issued by Water & Sewerage Companies (WaSCs), the typical maximum permissible concentration for total petroleum hydrocarbons (TPH) or mineral oil in condensate discharged to public foul sewer is 20 mg/L. Some WaSCs impose stricter limits (e.g. 10 mg/L) depending on local sewage treatment works capacity. Discharge without consent or exceeding consent limits is a criminal offence under Section 118 of the Water Industry Act 1991, punishable by fines up to £250,000 and/or disconnection. All sites with compressed air systems generating >50 L/day condensate must apply for trade effluent consent and install an approved oil-water separator (typically coalescer type) to achieve <20 mg/L before discharge. Environmental Permitting (England and Wales) Regulations 2016 also apply if discharge could impact surface water or groundwater.
UK best practice (aligned with ISO 14001 and BS EN ISO 8573 for compressed air quality) recommends: (1) Weekly visual inspection of separator for leaks, correct operation, and sump level; (2) Monthly effluent testing for TPH concentration using calibrated test kit (0–100 mg/L range); (3) Quarterly coalescer filter replacement (or sooner if effluent TPH exceeds 15 mg/L trigger level); (4) Annual full service by competent engineer (OEM-approved or IOSH/NEBOSH qualified), including pressure test, seal replacement, and calibration check. Records required: maintenance logbook with dates, operative names, and TPH test results; waste transfer notes for disposed filters/sludge (retain 3 years under Duty of Care Regulations); trade effluent consent certificate and quarterly monitoring reports submitted to WaSC; COSHH assessment for hydrocarbon exposure; and Permit-to-Work records for all maintenance activities. Environment Agency or WaSC inspectors may request these during site audit—failure to produce records can result in enforcement notice or prosecution.
Yes. Under the Pressure Systems Safety Regulations 2000 (PSSR), any work on a pressure system (including oil-water separators operating above atmospheric pressure, typically 7–10 bar) requires a Written Scheme of Examination and safe isolation before maintenance. A Permit-to-Work is mandatory for opening any pressurised component to prevent catastrophic release of condensate (risk of injection injury or hydrocarbon spray). LOTO (Lockout-Tagout) procedure must include: (1) Closing upstream isolation valve and applying personal padlock (BS EN ISO 14118 compliant); (2) Opening drain valve to depressurise system to 0 bar (verified by pressure gauge); (3) Tagging valve with 'DO NOT OPERATE' danger tag; (4) Independent verification by second competent person (Authorised Person under PSSR). Failure to isolate is a breach of PSSR 2000 Regulation 12 (safe operation) and HSW Act Section 2, and has resulted in prosecutions following injury incidents. All operatives must be trained in LOTO and hold evidence of competence (e.g. IOSH Working Safely, NEBOSH General Certificate, or manufacturer-specific training).
| Operative / Supervisor Name | Trade / Role & CSCS No. | Signature | Date & Time |
|---|---|---|---|
| 1. (Site Supervisor): | |||
| 2. | |||
| 3. | |||
| 4. |