This COSHH assessment addresses the safe handling, storage, and use of sulphuric acid (H₂SO₄) at 30-38% concentration, commonly used as battery electrolyte in industrial and automotive applications. The substance is classified under GHS05 (Corrosive) and presents significant risks including severe skin/eye burns, respiratory tract damage from mist inhalation, and hydrogen gas evolution during charging operations. This assessment is compliant with the Control of Substances Hazardous to Health Regulations 2002 (as amended), EH40/2005 Workplace Exposure Limit for sulphuric acid thoracic mist (0.05 mg/m³ 8-hour TWA), and the Dangerous Substances and Explosive Atmospheres Regulations 2002 (DSEAR) for hydrogen off-gassing hazards. Engineering controls including local exhaust ventilation (LEV), spill containment, emergency eyewash/shower stations, and explosion-proof electrical equipment in charging areas are mandatory. All personnel must complete COSHH awareness training and demonstrate competence in emergency response procedures before handling this substance.
| Identified Hazard & Harm | Initial Risk (L×S) | Mandatory Engineering, Isolation & Procedural Controls | Residual Risk |
|---|---|---|---|
| 1. Severe chemical burns from direct skin/eye contact with 30-38% sulphuric acid Harm: Full-thickness skin burns (Category 1A corrosive), permanent eye damage/blindness, scarring requiring skin grafts, potential fatality if large body surface area exposed | 4 × 5 = 20 | Engineering: Closed transfer systems with leak-proof connections. Administrative: Permit-to-work for bulk transfers, two-person rule for >5L quantities. PPE: Mandatory BS EN ISO 374-1 gloves, BS EN 166 face shield, Type 3/4 chemical suit. Emergency eyewash/deluge shower within 10m (BS EN 15154 compliant, tested weekly). Spill kits with neutralising agent (sodium bicarbonate) at all handling locations. | 2 × 4 = 8 |
| 2. Inhalation of sulphuric acid mist exceeding EH40/2005 WEL (0.05 mg/m³ thoracic fraction) Harm: Acute respiratory tract burns, pulmonary oedema, chronic bronchitis, dental erosion, reduced lung function (FEV1), potential long-term respiratory sensitisation | 4 × 4 = 16 | Engineering: LEV system with minimum 0.5 m/s capture velocity at source, tested/examined every 14 months per HSG258. Enclose mixing/pouring operations where practicable. Administrative: Air monitoring (personal/static) every 6 months, health surveillance (respiratory function tests) annually per COSHH Reg 11. RPE (P3 filter) mandatory if LEV fails or during maintenance. Restrict access to authorised personnel only. | 2 × 3 = 6 |
| 3. Hydrogen gas accumulation during battery charging creating explosive atmosphere (DSEAR hazard) Harm: Fire/explosion causing multiple fatalities, severe burns, structural damage, secondary acid spillage. Hydrogen LEL 4% v/v - invisible, odourless, rapid flame propagation | 3 × 5 = 15 | Engineering: ATEX-rated explosion-proof charging equipment (Zone 1/2 classification), continuous hydrogen monitoring with <1% LEL alarm/interlock shutdown. Forced ventilation achieving minimum 5 air changes/hour in charging areas. Administrative: DSEAR risk assessment reviewed annually, hot work permit system within 10m radius, no ignition sources signage. Electrical equipment bonding/grounding. Competent person inspections quarterly. | 2 × 4 = 8 |
| 4. Exothermic reaction and violent boiling when diluting acid (incorrect water addition sequence) Harm: Explosive boiling projecting hot acid causing facial/upper body burns, eye injuries, inhalation of concentrated acid vapour, potential for multiple casualties in confined spaces | 4 × 4 = 16 | Engineering: Dedicated dilution station with fixed water supply and acid dosing system preventing reverse addition. Administrative: Mandatory training on 'Acid to Water' rule with competency assessment. Written SOP displayed at dilution points: 'Always Add Acid to Water - Never Reverse'. Supervision required for operatives with <6 months experience. LOTO procedure for maintenance of dosing equipment. Temperature monitoring during dilution (max 60°C). | 1 × 4 = 4 |
| 5. Environmental contamination from acid spillage into drains/watercourses Harm: Aquatic toxicity (pH <2), watercourse pollution incident (Category 1/2), Environment Agency prosecution, ecological damage, remediation costs >£50k, reputational damage | 3 × 3 = 9 | Engineering: Secondary containment bunds (110% capacity) for all storage >50L, sealed impermeable flooring with trapped drainage to interceptor tank. Automatic pH monitoring on effluent discharge with fail-safe shutdown. Administrative: Weekly bund integrity inspections (documented), spill response plan with Environment Agency notification procedure (<24hrs for significant incidents). Staff training on spill containment (annual refresher). Neutralisation materials (lime/soda ash) stockpiled. Insurance-backed environmental liability cover. | 1 × 3 = 3 |
Review site-specific COSHH assessment and DSEAR zoning for work area. Obtain permit-to-work if transferring >25L or working in confined spaces. Verify emergency eyewash/shower operational (15-minute flow test). Don mandatory PPE in correct sequence: chemical suit/apron first, then face shield/goggles, finally gloves (ensure cuffs overlap sleeves). Confirm spill kit location and contents (neutraliser, absorbent pads, disposal bags). Check LEV system operational (visual airflow indicator). Ensure second person available for emergency assistance.
Use only designated acid-resistant transfer pump (polypropylene/PVDF). Verify container labelling (UN2796, GHS05 pictogram, concentration). Ground/bond containers before transfer to prevent static discharge. Position receiving container in bunded area with drip tray. Activate LEV system before opening containers. Transfer at controlled rate (<2 L/min) to minimise mist generation. Never use compressed air for transfer. Keep containers sealed when not actively transferring. Measure specific gravity (1.180-1.220 for 30-38%) to verify concentration.
Conduct dilution only in designated station with fixed water supply. ALWAYS ADD ACID TO WATER - NEVER REVERSE. Fill vessel to 60-70% capacity with cold water first. Slowly add acid in small increments (max 100ml at a time) while stirring continuously. Monitor temperature (must not exceed 60°C). Allow cooling between additions if temperature rises rapidly. Use face shield and stand to side of vessel (not directly over). Calculate volumes in advance using dilution formula. Never dilute in confined spaces due to vapour generation.
Ensure battery charging area has operational hydrogen detection system (<1% LEL alarm). Remove all ignition sources within 10m radius. Check electrolyte level using hydrometer (specific gravity 1.210-1.280 for charged battery). Top up with distilled water only (never add acid unless under supervision). Connect charger with battery disconnected from equipment. Verify ATEX-rated charger and explosion-proof ventilation operational. Monitor hydrogen levels throughout charge cycle. Do not disconnect during charging (spark risk). Allow 30-minute ventilation period post-charge before moving battery.
For spills <1L: Isolate area, don full PPE, contain with absorbent pads working from outside inward. Neutralise with sodium bicarbonate (add gradually until fizzing stops, pH 6-8). For spills >1L: Evacuate area, activate emergency response, prevent drain entry using bund/sandbags. Notify Environment Agency if risk of watercourse contamination. Use only trained spill response team for large volumes. Collect contaminated materials in acid-resistant containers (UN-approved). Label as hazardous waste (EWC code 16 06 06). Decontaminate area with copious water after neutralisation. Air monitoring required before re-entry.
Decontaminate tools/equipment with water rinse before storage. Remove PPE in reverse order: gloves first (peel inside-out), then face shield, finally suit/apron. Inspect PPE for damage/degradation - discard if compromised. Wash hands thoroughly with soap and water. Store acid in original labelled containers within bunded cabinet (segregated from alkalis, metals, organics). Complete permit close-out and usage log. Dispose of contaminated PPE/materials via licensed hazardous waste contractor (consignment note required). Update COSHH assessment if any near-miss or control failure occurred.
IMMEDIATE ACTIONS - Skin Contact: Remove contaminated clothing immediately while flooding affected area with water for minimum 15 minutes. Do not attempt to neutralise on skin. Seek medical attention urgently. Eye Contact: Irrigate eyes at eyewash station for minimum 15 minutes, holding eyelids open. Remove contact lenses if present and easy to do. Obtain emergency medical treatment - permanent damage occurs rapidly. Inhalation: Move casualty to fresh air immediately. If breathing is difficult, administer oxygen if trained. Seek medical attention if respiratory symptoms develop. Ingestion: DO NOT induce vomiting (risk of further oesophageal damage). Rinse mouth with water. Give small amounts of water to drink if conscious. Seek immediate medical attention. Fire/Explosion (Hydrogen): Evacuate area, activate fire alarm, call 999. Do not attempt firefighting unless trained. Use water spray to cool containers. Approach from upwind. Inform fire service of hydrogen and acid hazards. Major Spill: Evacuate area, prevent drain entry, notify Environment Agency Incident Hotline (0800 807060) if environmental release. All incidents require completion of HSE RIDDOR notification if injury results in >7 days absence or specified injury occurs. Maintain emergency contact list including: Occupational Health, Poison Centre (0344 892 0111), Environment Agency, and nearest A&E with chemical burns capability.
Under COSHH Regulation 11, health surveillance is mandatory where exposure to sulphuric acid mist may cause identifiable disease/adverse health effect and there is reasonable likelihood of occurrence under working conditions. Given the EH40/2005 WEL of 0.05 mg/m³ (8-hour TWA thoracic fraction) and the potential for respiratory sensitisation and dental erosion, employers must provide: (1) Initial baseline respiratory function testing (spirometry) before first exposure; (2) Annual respiratory questionnaires and lung function tests for all regularly exposed workers; (3) Dental examinations every 6-12 months where mist exposure occurs; (4) Biological monitoring is not applicable for sulphuric acid. Records must be retained for 40 years post-exposure. If air monitoring demonstrates consistent exposure below 50% of WEL (0.025 mg/m³) with robust controls, surveillance frequency may be reduced following competent occupational health advice, but cannot be eliminated entirely due to the corrosive nature of the substance.
DSEAR 2002 requires a formal risk assessment for any work activity that could create an explosive atmosphere. During lead-acid battery charging, hydrogen evolution occurs (approximately 0.05L H₂ per Ah of charge). Compliance requires: (1) ATEX workplace zoning - typically Zone 2 (explosive atmosphere unlikely in normal operation) for general charging areas, Zone 1 (likely to occur) within 0.5m of battery vents during charging; (2) All electrical equipment within hazardous zones must be ATEX-certified (Ex rating appropriate to zone); (3) Continuous or frequent hydrogen monitoring with alarm set at <1% LEL (4% v/v) and automatic charger shutdown at 1% LEL; (4) Mechanical ventilation achieving minimum 5 air changes/hour, with failure alarm; (5) Elimination of ignition sources (no smoking, hot work permit system, non-sparking tools); (6) Competent person verification of ATEX compliance annually; (7) Staff training on DSEAR hazards and emergency procedures. The DSEAR assessment must be reviewed if processes change or following any incident. Integration with COSHH assessment is essential as both hydrogen (DSEAR) and acid mist (COSHH) hazards coexist.
LEV systems controlling sulphuric acid mist exposure must comply with COSHH Regulation 9 (control measures) and Regulation 9(2) (maintenance). Specific requirements include: (1) Design: Minimum capture velocity of 0.5 m/s at the source (higher for vigorous processes), acid-resistant ductwork (polypropylene/FRP), and discharge to safe location away from air intakes; (2) Thorough Examination and Test (TExT): Mandatory every 14 months by competent person (HSG258 guidance), with written report retained for 5 years. Examination must verify adequate capture velocity, structural integrity, and filter efficiency; (3) Routine Checks: Weekly visual inspection by operator (airflow indicator, unusual noise/vibration), documented in log; (4) Performance Testing: Initial commissioning test to verify achievement of WEL, then repeat if process changes or TExT identifies deficiencies; (5) Maintenance: Immediate repair if defect identified - interim RPE (P3 filter) mandatory if LEV unavailable and work must continue. Filters must be changed per manufacturer schedule (typically 6-12 months) and disposed as hazardous waste. Failure to maintain LEV resulting in WEL exceedance is an HSE enforcement priority and may result in Improvement/Prohibition Notices or prosecution under Section 33 HSWA 1974.
Competent Person & Operative Declaration: By signing below, the Site Supervisor confirms this assessment has been adapted and verified for actual site conditions, and operatives confirm they have attended the pre-start Toolbox Talk for Sulphuric Acid (30-38% Battery Electrolyte) & Hydrogen Off-Gassing Control and will follow the safe system of work.