This COSHH assessment addresses the safe handling, storage, and use of peracetic acid (PAA) based sanitiser and Clean-In-Place (CIP) disinfectant solutions containing 5-15% peracetic acid and hydrogen peroxide. Peracetic acid is classified as oxidising (GHS03), corrosive (GHS05), and hazardous to the aquatic environment (GHS09) under CLP Regulation. This document provides comprehensive control measures for decanting, dilution, CIP system charging, and emergency response procedures. The assessment complies with COSHH 2002 (as amended), CLP Regulation (EC) No 1272/2008, and DSEAR 2002. All personnel must complete competency-based training before handling this substance. Engineering controls including local exhaust ventilation (LEV), closed transfer systems, and segregated storage are mandatory. Emergency eyewash and deluge shower facilities must be accessible within 10 seconds of work areas. This assessment must be reviewed annually or following any incident, process change, or regulatory update.
| Identified Hazard & Harm | Initial Risk (L×S) | Mandatory Engineering, Isolation & Procedural Controls | Residual Risk |
|---|---|---|---|
| 1. Severe chemical burns from skin/eye contact with concentrated peracetic acid solution (5-15%) Harm: Immediate severe skin corrosion, permanent eye damage/blindness, scarring, long-term disability. H314 classification requires immediate medical intervention. | 4 × 5 = 20 | Engineering: Install closed transfer systems with leak-proof connections; provide emergency eyewash/deluge shower within 10m (10-second access). Administrative: Implement permit-to-work for bulk transfers; limit container sizes to 25L maximum for manual handling; display emergency procedure signage at all handling points. PPE: Mandatory chemical-resistant gloves (BS EN ISO 374-1 Type A), full-face protection (BS EN 166), Type 3/4 coveralls (BS EN 14605). Training: Annual competency assessment on emergency response and first aid for chemical burns. | 2 × 4 = 8 |
| 2. Respiratory irritation and acute inhalation injury from peracetic acid vapour exposure during decanting or CIP operations Harm: Coughing, throat irritation, bronchospasm, pulmonary oedema in severe cases. H335 classification. WEL: 0.4 ppm (15-min STEL) - easily exceeded in poorly ventilated areas. | 4 × 3 = 12 | Engineering: Install local exhaust ventilation (LEV) at all decanting points achieving minimum 0.5 m/s capture velocity; conduct TM44 LEV examination every 14 months. Use closed CIP systems with vapour containment. Administrative: Implement atmospheric monitoring before confined space entry; establish exclusion zones during bulk transfers; rotate personnel to limit exposure duration. Respiratory Protection: FFP3 respirator (BS EN 149:2001) for emergency response only - not routine control. Ventilation is primary control per COSHH hierarchy. | 2 × 2 = 4 |
| 3. Fire intensification and violent reaction with incompatible materials (oxidising hazard H272) Harm: Accelerated combustion of organic materials, explosive decomposition if contaminated with metals/reducing agents, facility fire, multiple casualties. | 3 × 5 = 15 | Engineering: Segregated storage in dedicated chemical store with 3m separation from combustibles, reducing agents, and alkalis; install temperature monitoring with alarm set at 20°C; use ATEX-rated equipment in storage areas. DSEAR compliance: Conduct hazardous area classification (Zone 2 minimum); eliminate ignition sources within 5m radius. Administrative: Implement chemical compatibility matrix; prohibit storage above 25°C; inspect containers weekly for decomposition signs (gas generation, discolouration); maintain spill containment capacity of 110% largest container. LOTO: Isolate and lock-off CIP systems before maintenance. | 2 × 3 = 6 |
| 4. Acute toxicity from accidental ingestion or aspiration during siphoning/decanting (H302 Harmful if swallowed) Harm: Severe oral/oesophageal burns, gastrointestinal perforation, aspiration pneumonitis, potential fatality. Immediate medical emergency. | 2 × 5 = 10 | Engineering: Use pump transfer systems only - prohibit siphoning by mouth or gravity decanting without anti-siphon devices. Install clearly labelled dedicated chemical taps with non-return valves. Administrative: Enforce strict 'no eating/drinking/smoking' policy in chemical handling areas; provide separate welfare facilities; implement buddy system for all chemical transfers. Emergency: Display Toxbase access details and product SDS at all handling locations; establish direct communication with NHS 111/999 for chemical exposure incidents. Training: Include recognition of ingestion symptoms and emergency first aid in induction. | 1 × 4 = 4 |
| 5. Environmental contamination from spillage or improper disposal (H400 Very toxic to aquatic life) Harm: Watercourse pollution, aquatic ecosystem destruction, prosecution under Environmental Protection Act 1990, unlimited fines, director liability. | 3 × 4 = 12 | Engineering: Install bunded storage with 110% capacity and impermeable flooring; fit automatic shut-off valves on transfer lines; provide sealed drainage system with interceptor trap. Administrative: Implement environmental incident response plan with Environment Agency notification procedure (0800 807060); maintain spill kit inventory with monthly checks; prohibit drain disposal - arrange licensed hazardous waste collection (EWC code 20 01 19); neutralise small spills with sodium thiosulphate before recovery. Training: Annual environmental awareness training covering legal duties and incident reporting. Monitoring: Conduct quarterly drain sampling if discharge consent applies. | 1 × 3 = 3 |
Conduct dynamic risk assessment and complete permit-to-work if required for bulk transfers. Verify emergency eyewash/deluge shower is functional (weekly test record check). Confirm LEV system operational (check airflow indicator). Clear 2m exclusion zone around work area and erect warning barriers. Inspect all PPE for damage: check gloves for perforations using water test, ensure face shield/goggles have clear vision, verify coveralls have no tears. Don full PPE in correct sequence: coveralls first, then boots, gloves, and face protection last. Ensure second person (buddy) is present and briefed on emergency procedures. Verify spill kit location and contents. Check product label and SDS batch number match. Confirm storage temperature has not exceeded 25°C (check temperature log).
Position container on stable, level surface within bunded area or over spill tray (minimum 30L capacity). Inspect container for bulging, discolouration, or gas generation indicating decomposition - if present, DO NOT OPEN and contact supplier immediately. Slowly loosen cap to release any pressure build-up (face cap away from body and others). Listen for hissing - if excessive pressure detected, re-seal and allow to vent in controlled manner. Once pressure equalised, remove cap completely and inspect contents: solution should be clear to pale yellow; reject if cloudy, contains sediment, or has strong acrid odour (indicates decomposition). Check concentration using test strips - verify within specification (5-15%). Record batch number, concentration, and inspection findings. Keep container opening time to minimum to reduce vapour release.
For bulk transfers: Connect closed transfer pump system ensuring all connections are secure and compatible (PTFE/Viton seals). Conduct leak test by running system at low flow before full operation. Position receiving vessel in secondary containment. For manual decanting: Use dedicated chemical-resistant jug with pouring spout; never pour from height - keep spout in contact with receiving vessel rim to minimise splashing and vapour generation. Decant slowly and steadily - maximum 2L per minute to control vapour release. Maintain face shield protection and ensure LEV capture hood is positioned within 300mm of pour point. Never fill containers more than 90% capacity to allow for thermal expansion. Label receiving containers immediately with contents, concentration, date, and hazard symbols. Replace caps on both source and receiving containers immediately after transfer to minimise vapour exposure.
Verify CIP system is isolated and depressurised before adding chemicals (check pressure gauge reads zero). Confirm dosing pump calibration is current (maximum 6-month interval). Calculate required volume based on system capacity and target concentration (typically 100-200 ppm for sanitisation). Add peracetic acid solution to CIP tank using closed dosing system or via dedicated fill point with funnel and splash guard. Start circulation pump and allow 5 minutes mixing time. Sample from designated sampling point using appropriate sampling equipment (avoid hand contact). Test concentration using calibrated test strips or meter - adjust if outside specification range. Record concentration, time, temperature, and operator initials in CIP log. Verify all system valves are correctly positioned per CIP SOP before commencing automated cycle. Ensure personnel are clear of spray zones before system activation.
Rinse all transfer equipment with copious water immediately after use (minimum 2 minutes continuous rinse). For equipment with residual peracetic acid, neutralise using sodium thiosulphate solution (10% w/v) until test strips show <10 ppm residual. Dispose of rinse water via designated chemical drain with interceptor (if available) or collect for licensed disposal - NEVER dispose to surface water drains. Clean spill tray/bunded area with water and inspect for any residual chemical. Store empty containers in designated hazardous waste area with caps replaced - do not rinse empty containers as this creates larger volume of contaminated waste. Complete waste consignment note for licensed collection (EWC code 20 01 19 for empty containers, 16 05 06 for laboratory chemicals). Inspect PPE for contamination - if splashed, rinse thoroughly before removal; dispose of heavily contaminated PPE as hazardous waste. Wash hands and forearms thoroughly with soap and water after PPE removal.
Return peracetic acid containers to dedicated chemical store immediately after use - never leave unattended in work areas. Store in original containers in bunded area with 3m separation from incompatible materials (acids, alkalis, reducing agents, metals, organic materials). Ensure storage temperature does not exceed 25°C - check and record temperature in storage log. Position containers on lower shelves (maximum 1m height) to minimise fall risk. Ensure adequate ventilation in storage area (minimum 5 air changes/hour). Lock chemical store and restrict access to authorised personnel only. Complete COSHH task record including: date, time, product batch, quantity used, concentration achieved, any incidents/near-misses, and operator signature. Report any adverse health effects (skin irritation, respiratory symptoms, eye irritation) to line manager and occupational health immediately. Update chemical inventory system. Review and sign off permit-to-work if applicable.
EMERGENCY CONTACTS: Emergency Services: 999 | Environment Agency Incident Hotline: 0800 807060 | NHS 111 (non-emergency medical advice) | Toxbase: www.toxbase.org (for healthcare professionals) | Supplier Emergency Line: [Insert 24/7 technical support number] FIRST AID PROCEDURES: SKIN CONTACT: Remove contaminated clothing immediately while rinsing. Rinse affected area with copious running water for minimum 15 minutes - continue rinsing during transport to medical facility. DO NOT attempt to neutralise on skin. Cover with sterile dressing if available. Seek immediate medical attention - inform medical personnel of chemical name and concentration. Treat as thermal burn requiring specialist assessment. EYE CONTACT: Immediately irrigate eyes with lukewarm water for minimum 15 minutes, holding eyelids open. Remove contact lenses if present and easy to do. Continue rinsing during transport. DO NOT use neutralising agents in eyes. This is a medical emergency requiring immediate hospital treatment - permanent blindness can result from delayed treatment. Call 999 for ambulance. INHALATION: Remove casualty to fresh air immediately. Keep at rest in semi-upright position to ease breathing. If breathing is difficult, administer oxygen if trained and equipment available. If breathing stops, commence CPR if competent. Call 999 immediately. Monitor for delayed pulmonary oedema (can develop up to 48 hours post-exposure) - all significant inhalation exposures require hospital assessment even if initially asymptomatic. INGESTION: DO NOT induce vomiting (risk of aspiration and further oesophageal damage). Rinse mouth with water and spit out - do not swallow. Give small sips of water if conscious and able to swallow. Call 999 immediately and inform of chemical ingestion. Position casualty in recovery position if consciousness impaired. This is a life-threatening emergency requiring immediate hospital treatment. SPILLAGE PROCEDURES: MINOR SPILL (<1L): Evacuate non-essential personnel. Ensure adequate ventilation. Don full PPE including respiratory protection if vapour present. Contain spill with absorbent pads/granules working from outside inward. Neutralise with sodium thiosulphate solution (10% w/v) - test with pH paper until neutral. Collect contaminated absorbent in sealed container labelled as hazardous waste. Rinse area with water and dispose via chemical drain or collect for disposal. Ventilate area for minimum 30 minutes before normal operations resume. MAJOR SPILL (>1L): Evacuate area immediately and establish 10m exclusion zone. Eliminate all ignition sources. Call emergency services (999) if risk to personnel, environment, or if spill cannot be safely contained. Alert Environment Agency (0800 807060) if any risk of watercourse contamination. Only trained spill response team with appropriate PPE and respiratory protection should attempt containment. Use absorbent booms to contain spill and prevent drain entry. Cover with absorbent material and neutralise cautiously with sodium thiosulphate. Collect as hazardous waste. Ventilate area thoroughly before re-entry. FIRE INVOLVING PERACETIC ACID: Evacuate immediately - peracetic acid is oxidising and will intensify fire. Call 999 and inform fire service of oxidising chemical involvement. If safe to do so, remove containers from fire area. DO NOT use water jets directly on containers (risk of violent reaction). Use water spray to cool containers from protected position. Firefighting should only be attempted by trained fire service personnel with appropriate breathing apparatus. Decomposition products include toxic vapours - maintain upwind position. REPORTING: All incidents involving peracetic acid exposure (skin/eye contact, inhalation, spillage >1L, environmental release) must be reported immediately to line manager and recorded in accident book. RIDDOR-reportable injuries (hospitalisation >24 hours, specified injuries including chemical burns) must be reported to HSE within required timescales. Conduct incident investigation and review COSHH assessment following any exposure incident.
Competent Person & Operative Declaration: By signing below, the Site Supervisor confirms this assessment has been adapted and verified for actual site conditions, and operatives confirm they have attended the pre-start Toolbox Talk for Peracetic Acid (5-15%) Peroxide Sanitiser & CIP Disinfectant Handling and will follow the safe system of work.
| Operative / Supervisor Name | Trade / Role & CSCS No. | Signature | Date & Time |
|---|---|---|---|
| 1. (Site Supervisor): | |||
| 2. | |||
| 3. | |||
| 4. | |||
| 5. | |||
| 6. |